In this second part of the testing I am replicating a few typical scenarios for recharging on a cruising boat. No one wants to run the engine or generator for very long so I wanted to illustrate what kind of energy can be stored in the AGM battery at a 2 hour time interval at a .2C charge rate.
This test started with a discharge from 100% SOC to 50% SOC with the battery delivering 47.85Ah at a 5.25A constant current load. The battery was then recharged for exactly 2 hours at .2C and then immediately discharged back to 50% SOC and the stored energy for that cycle was measured.
The charge rate for this test was 21A and the timer set for 2 hours. If the battery could stay in bulk for two hours our maximum potential energy into the battery would be 42A. Because the battery hit absorption voltage, before hitting the 2 hour mark, we simply can not get 42Ah of energy into the battery...